Calculation of Stainless Steel Duct Dimensions

Aug 10, 2026 Leave a message

Duct Size = Airflow Rate / Air Velocity
Airflow Rate = Room Area × Room Height × Air Change Rate
Example: Airflow rate of 40,000 m³/h, air velocity of 9 m/s:
Duct Size = 40,000 / 9 / 3,600 ≈ 1.23 m²
1.23 ≈ 1.5 × 0.82
Therefore, the duct size is 1500 mm × 800 mm.


Steps for calculating duct diameter:
1. Draw an isometric view of the ventilation or air conditioning system; number each duct section and mark its length and airflow rate. Duct section length is generally calculated based on the distance between the centerlines of the two fittings, without deducting the length of the fittings themselves (e.g., tees, elbows).
2. Determine a reasonable air velocity.
Air velocity within the duct significantly impacts the economic efficiency of ventilation and air conditioning systems. High velocity allows for smaller duct cross-sections, resulting in reduced material usage and lower construction costs; however, it increases system resistance and power consumption, thereby raising operating costs. In dust removal systems, high velocity accelerates wear on equipment and ducts, while in air conditioning systems, it increases noise levels. Conversely, low velocity results in lower resistance and reduced power consumption; however, it requires larger duct cross-sections, leading to higher material and construction costs and increased space requirements. In dust removal systems, excessively low velocity can cause dust to settle and clog the ducts.